Technical specification

Sensing Input 
Voltage 190-264V ac max, 1 phase, 2 wire 
Frequency  50-60 Hz nominal 

Power Input (PMG)
Voltage 140-220V ac max, 3 phas, 3 wire 
Current 3A/phase 
Frequency 100-120Hz nominal 

Output 
Voltage max 120V dc 
Current continuous 2.7 A
Intermittent 6A for 10 secs.
Resistance 15 ohms minimum 

Regulation 
 +/- 1%  (see note 1)

Thermal Drift 
 0.03% per °C change in AVR  ambient (note 2)

Soft start ram time 
 3 seconds 

Typical system response 
 AVR Response 10 ms 
Filed current to 90% 80 ms 
Machine Volts to 97% 300 ms 

 External voltage adjustment
 +/- 10% with 1 k ohm 1 watt trimmor (see note 3)

Under frequency protection 
 Set point 95% Hz (see note 4) 
Slope 170% down to 30 Hz 

 Unit power dissipation 
 12 watts maximum 

Analogue input 
 Maximum input +/- 5V dc (see note 5)
Sensitivity: 0.07 A for 5% droop OPF
Max. input: 0.33 A 

Over excitation protection 
 Set point 75 V dc 
Time delay 10 seconds (fixed)

 Environmental 
 Vibration  20-100 Hz 50mm/sec
100Hx - 2kHz 3.3g
Operating temperature -40 to +70°C

Relative humidity 0-70°C 95% (see note6)
Storage temperature -55 to +80°C

Notes 
1. With 4% engine governing.
2. After 10 minutes 
3. Applies to mod status D onwards. Generator de-rate may 
amply. Check with factory.
4. Factory set, semi-sealed, jumper selectable.
5. Any device connected to the analogue input must be fully 
floating (galvanically isolated from ground), with an 
insulation strenght of 500V ac
6. Non condensing.