domingo, 16 de agosto de 2015

Introduction 



Sensing Input 
Voltage 60- 510 VAC single phase 2 wires 
voltage is DIP switch selectable 
Frequency  50 / 60 Hz, DIP  switch selectable 

Power Input
Voltage 60 - 300 VAC, single phase 2 wires 

Output 
Voltage Max. 90 VDC  @ 240 VAC input 
Corrent Continuos 16A 
Intermittent 20A for 10 sec 
Resistance Min. 5 ohm 

Voltage regulation 
 Residual voltage at AVR terminal > 5 VAC 

Thermal Drift 
0,03% per °C change in AVR ambient 

Load Current Compensation 
1A or 5A Max. 7% @ PF0.5 DIP Switch Selectable 

Analogue Voltage Input 
Max. +/-10% @ +/-3VDC

Over Excitation Protection 
Max.10 watt

External Volts Adjustment 
+/- 5 % with 2K ohm 1 whatt trimmer 

Unit Power Dissipation 
 Max. 10 watt 

Under Frequency Protection (Factory Setting)
 50/60 Hz DIP SW selectable 

Soft Start Ramp Time 
 2 sec.

Dimensions 
 156mm L * 106mm W * 41mm H 

Weight 
 450g +/- 2% 