sábado, 27 de junio de 2015

Features 

  • > +/- 1% Regulation 
  • 110/220/400 VAC Programmalble Input 
  • Rugged Compact Design 
  • With Under Frequency Protection 
  • Soft  Start Voltage Ramping 
  • EMI Suppression 
  • Built- in Hihg Capacity 8 Amp Fuse 

Specifications 


Sensinglnput  voltage: 110/220/400VAC, 1phase2wire  voltageBuild-up  Resedualvolts at AVR terminal >5VAC

Power Input  voltage: 100~260VAC ,1phase 2wire external Volts Adjustment +/-7% whit 1K 1 watt trimmer 

Output voltage: Max.90 VDC@240VACinput Sotf Start Ramp Time 2sec.

Current Continuous3A Unit Power Dissipation Max.8Watt

Intermittent: 5A for 10SEE. EMI Suppression  Internal Electromagnetic Interference Filtering 

Resistance: Min.15 Max.100  Thermal. Drift 0.03%perC° change in AVR ambient 

Under Frequency Protection: 60Hz system presets knee point at 55Hz 

(Factory Setting) 50Hz system presents knee point at 45Hz 

Volts Regulation>1%(with 4% engine governing)