sábado, 27 de junio de 2015


Technical spcification 



INPUT 

Voltage: 
jumper selectable 
95-132V ac or 
190-264 ac 

Frequency:
50-60 Hz nominal 

Phase: 1 

OUTPUT 

Voltage:Max 90 dc at 207V ac input Current:Continuous 4 A cd Intermittent 6 A for 10 secs Resistance:
15 ohms minimum 

REGULATION 
+/- 1.0% (see note 1)

THERMAL DRIFT 

0.05% per deg. C change in AVR ambient (note 2)

TYPICAL SYSTEM RESPONSE

AVR  Response  20ms 
Filed current to 90% 80 ms 
Machine Volts to 97% 300ms 

EXTERNAL VOLTAGE ADJUSTMENT 

+/-10% whit 1 k ohm 1 watt trimmer (see note 3)

UNDER FREQUENCY PROTECTION 

Set point 95% Hz (see note 4) 
Slope 170 % down to 30 Hz 

UNIT POWER DISSIPATION 

10 watts maximum 

BUILD UP VOLTAGE 

4 Volts @ AVR terminals 

ENVIRONMENTAL

Vibration: 
20-100 Hz 50mm/sec
100Hz 2kHz 3.3g

Operating temperature:
-40 to +70C

Relative Humidity:
0-70C 95% (see note 5)

Storage temperature:
-55 to +80C 









0 comentarios: