On 12:07 by Unknown in AVR, Generadores, Oaxaca, Piezas para Generadores, Regulador, Regulador Automático de Voltaje, Venta No comments
Technical specification
Sensing Input
Voltage 190-264V ac max, 1 phase, 2 wire
Frequency 50-60 Hz nominal
Power Input (PMG)
Voltage 140-220V ac max, 3 phas, 3 wire
Current 3A/phase
Frequency 100-120Hz nominal
Output
Voltage max 120V dc
Current continuous 2.7 A
Intermittent 6A for 10 secs.
Resistance 15 ohms minimum
Regulation
+/- 1% (see note 1)
Thermal Drift
0.03% per °C change in AVR ambient (note 2)
Soft start ram time
3 seconds
Typical system response
AVR Response 10 ms
Filed current to 90% 80 ms
Machine Volts to 97% 300 ms
External voltage adjustment
+/- 10% with 1 k ohm 1 watt trimmor (see note 3)
Under frequency protection
Set point 95% Hz (see note 4)
Slope 170% down to 30 Hz
Unit power dissipation
12 watts maximum
Analogue input
Maximum input +/- 5V dc (see note 5)
Sensitivity: 0.07 A for 5% droop OPF
Max. input: 0.33 A
Over excitation protection
Set point 75 V dc
Time delay 10 seconds (fixed)
Environmental
Vibration 20-100 Hz 50mm/sec
100Hx - 2kHz 3.3g
Operating temperature -40 to +70°C
Storage temperature -55 to +80°C
Notes
1. With 4% engine governing.
2. After 10 minutes
3. Applies to mod status D onwards. Generator de-rate may
amply. Check with factory.
4. Factory set, semi-sealed, jumper selectable.
5. Any device connected to the analogue input must be fully
floating (galvanically isolated from ground), with an
insulation strenght of 500V ac
6. Non condensing.
sábado, 27 de junio de 2015
On 13:39 by Unknown in AVR, Generadores, Oaxaca, Piezas para Generadores, Regulador, Regulador Automático de Voltaje, Venta. 2 comments
Features
- > +/- 1% Regulation
- 220/440 VAC Programmable Input
- Rugged Compact Desingn
- Whit Under Frequency Protection
- Soft Stars Voltage Ramping
- EMI Suppression
- Built-in Hihg Capacity 10 Amp Fuse
Specifications
Sensinglnput voltge: 180~260VAC,1phase 2wire voltageBuild-up Residualvolts at AVR terminal>5VACResistance: Min.12 Max.100 Thermal. Drift 0.03%per C°chage in AVR ambient
On 12:45 by Unknown in AVR, Generadores, Oaxaca, Piezas para Generadores, Regulador, Regulador Automático de Voltaje, Venta No comments
Features
- > +/- 1% Regulation
- 110/220/400 VAC Programmalble Input
- Rugged Compact Design
- With Under Frequency Protection
- Soft Start Voltage Ramping
- EMI Suppression
- Built- in Hihg Capacity 8 Amp Fuse
Specifications
(Factory Setting) 50Hz system presents knee point at 45Hz

On 11:28 by Unknown in AVR, Generadores, Piezas para Generadores, Regulador Automático de Voltaje, Venta No comments
Technical spcification
INPUT
Voltage:
jumper selectable
95-132V ac or
190-264 ac
Frequency:
50-60 Hz nominal
Phase: 1
OUTPUT
Voltage:Max 90 dc at 207V ac input Current:Continuous 4 A cd Intermittent 6 A for 10 secs Resistance:
15 ohms minimum
REGULATION
+/- 1.0% (see note 1)
THERMAL DRIFT
0.05% per deg. C change in AVR ambient (note 2)
TYPICAL SYSTEM RESPONSE
AVR Response 20ms
Filed current to 90% 80 ms
Machine Volts to 97% 300ms
EXTERNAL VOLTAGE ADJUSTMENT
+/-10% whit 1 k ohm 1 watt trimmer (see note 3)
UNDER FREQUENCY PROTECTION
Set point 95% Hz (see note 4)
Slope 170 % down to 30 Hz
UNIT POWER DISSIPATION
10 watts maximum
BUILD UP VOLTAGE
4 Volts @ AVR terminals
ENVIRONMENTAL
Vibration:
20-100 Hz 50mm/sec
100Hz 2kHz 3.3g
Operating temperature:
-40 to +70C
Relative Humidity:
0-70C 95% (see note 5)
Storage temperature:
-55 to +80C
domingo, 21 de junio de 2015
On 18:17 by Unknown in AS440, AVR, Generadores, Oaxaca, Piezas para Generadores, Regulador, Regulador Automático de Voltaje, Venta No comments
Technical specification
SENSISING INPUT
Voltage:
Jumper Selectable
100- 130 Vac 1 phase or
190-264 Vac 1 phase
Frequency: 50-60 Hz nominal
POWER INPUT
Voltage: 100-264 V ac 1 phase
Frequency: 50-60 Hz nominal
OUTPUT
Voltage: 82 V d.c. @ 200 V a.c.
Current: continuous 4A (see note 1). transient 7.5A for 10 secs.
Resistance: 15 ohms min ( 10 ohms min whent input volts is less than 175 ac)
REGULATION
+/- 1.0% (see note 2)
THERMAL DRIFT
.0.03% per deg . C change in AVR ambient (see note 3)
TYPICAL SYSTEM RESPONSE
AVR response 20 ms
Filed current to 90% 80 ms
Marchine Volts to 97% 300 ms
EXTERNAL VOLTAGE ADJUSTMENT
+/-10% winth 1 k ohm 1 watt trimmer (see note 4 )
increasing resistance lowers voltage.
UNDER FREQUENCY PROTECTION
Set point: 94 -98% Hz (see note 5)
UNIT POWER DISSIPATION
12 watts maximun
BUILD UP VOLTAGE
4 volts @ AVR terminals
ANALOGUE INPUT
Maximum input: +/- 5 Vdc (see note 6)
Sensitivity: 1V for 5% generator volts (adjustable)
Input resistance: 1 k ohm
QUADRATURE DROOP INPUT
10 ohms burden
Max. sensitivity: 0.07 A for 5% droop OPF
Max. input: 0.33 A
OVER EXCITATION PROTECTION
Set point: 75 V dc
Time delay: 10-15 seconds (fixed)
ENVIRONMENTAL
Vibration: 20 -100 Hz 50mm/sec 100Hz- 2kHz 3.3g
Operating temperature: -40 lo + 70C (note 7)
Storage temperature: -55 to +80Cjueves, 11 de junio de 2015
On 1:25 by Unknown in 15A, AVR, Piezas para Generadores, Regulador, Regulador Automático de Voltaje, Venta No comments
IMPORTANTE:
>Todos los reguladores que vendemos son nuevos importados por nosotros
>Conseguimos cualquier modelo que necesiten contactando por medio de nuestra pagina
domingo, 1 de marzo de 2015
On 14:16 by Unknown in 12A, AVR, Generadores, Piezas para Generadores, Regulador, Regulador Automático de Voltaje, Venta No comments
Suscribirse a:
GLOPMAR
Search
Formulario de contacto
Popular Posts
-
Technical Data Regulation Accuracy +/- 0.5% rated steady state conditions Voltage Drift: +/- 0.5% voltage change, fo...
-
TECHNICAL DATA Precisione di regolazione: +/-0.5% a regime, per valori di tensione e carico nominali steady state conditions, ...
-
SPECIFICATION Normal AVR supply power, 2 auxiliary windings (X1, X2, and Z, Z2) Shunt supply : 150 - 50/60Hz Rated...
-
Introduction Sensing Input Voltage 60- 510 VAC single phase 2 wires voltage is DIP switch selectable Frequency 50 / 60 ...
-
INTRODUCTION The AVC63-4 voltage regulator is an encapsulated electronic voltage regulator that controls the output of a b...